Chiller Systems

Reciprocating Compressors - Operating Costs

General

For example, an air-cooled chiller serving a hospital operating room suite that operates year-round could well have a lower annual electric cost than a comparable water-cooled unit, due to the large number of operating hours the unit will be operating at part-load and low-ambient temperature conditions. Only a careful energy use analysis of each application performed by a qualified professional can identify the most economical equipment choice.

Maintenance costs must also be factored in. Here are some typical mid-1995 $ per ton annual values.

Chiller Type 20 Tons 50 Tons 75 Tons 100 Tons 150 Tons 200 Tons
Water Cooled $79 $67 $58 $51 $40 $35
Air Cooled $70 $50 $45 $43 $35 $31

If the chiller is driven by a natural gas engine, the added maintenance costs of the engine must also be included. Typically this amounts to about $0.012 per ton per operating hour.

Compare - Operating and Maintenance Costs - Chillers